Heating Sequence of Operation:

  • When thermostat calls for heat, combustion air inducer starts.
  • Combustion air pressure switch proves inducer operation.
  • After pre-purge (approx. 30 seconds), spark ignition energizes and solenoid valves open.
  • Spark ignites gas, ignition sensor proves flame, and combustion continues.
  • If flame not detected after 10-second trial, controller repeats ignition sequence twice before lockout (60 minutes).
  • Burners must light without crossover delay, flames predominantly blue and centered.
  • Fan energizes approximately 30 seconds after ignition.
  • When thermostat satisfied, gas valve closes; combustion air inducer shuts off after 30 seconds.
  • System fan shuts off approximately 150 seconds after gas valve de-energizes.

Troubleshooting and error codes

LED Status Table

Status Table (Responsive)

LED UNIT OPERATION
Slow Flash* Normal Operation - No call for heat
Fast Flash Normal Operation - Call for heat
2 Flashes System lockout - failed to detect or sustain flame
3 Flashes Pressure switch failed closed before CAI is energized or failed open after CAI is energized
4 Flashes High limit (S10) switch open
5 Flashes Flame sensed and gas valve (GV1) not energized
6 Flashes On-board microprocessor fault.
7 Flashes Pressure switch (S18) closed with inducer off.
8 Flashes Rollout switch (S47/S195) open. Cycle-power to reset.
Steady On Control board (A3) failure
Steady Off Internal control board (A3) failure or not power.

Troubleshooting and error codes

LED Status Table

Status Table (Responsive)

LED UNIT OPERATION
Slow Flash* Normal Operation - No call for heat
Fast Flash Normal Operation - Call for heat
2 Flashes System lockout - failed to detect or sustain flame
3 Flashes Pressure switch failed closed before CAI is energized or failed open after CAI is energized
4 Flashes High limit (S10) switch open
5 Flashes Flame sensed and gas valve (GV1) not energized
6 Flashes On-board microprocessor fault.
7 Flashes Pressure switch (S18) closed with inducer off.
8 Flashes Rollout switch (S47/S195) open. Cycle-power to reset.
Steady On Control board (A3) failure
Steady Off Internal control board (A3) failure or not power.