Normal Sequence of Operation:

  • Thermostat calls for heat.
  • Circulator activates to monitor water temperature.
  • If thermostat cannot be satisfied, damper activates.
  • Ignition system starts and burner ignites.
  • Boiler heats water to setpoint.
  • Burner deactivates, heating cycle completes.
  • Circulator continues to operate until thermostat is satisfied.

Troubleshooting and error codes

Error Codes
Error Code Number Definition Consequence
4 Flame current too low. Check for flame. Non critical alarm
6 Flame sensed out of normal sequence (before opening or after closing gas valve). Soft lockout
18 Gas valve relays welded. Five consecutive soft lockouts. Hard lockout
23 Flame sensed during prepurge (before gas valve signaled opened). Soft lockout
32 Sensor 1 error. Temperature sensor in well is not reading correctly. Verify it is connected to board. Replace if necessary. Wait for recovery
55 Atmospheric damper end switch failed to close (end switch contacts stuck open). Wait for recovery
56 Atmospheric damper end switch failed to open (end switch contacts stuck close). Wait for recovery
57 Igniter flame rod shorted to burner ground Wait for recovery
58 Igniter flame rod shorted to burner ground. Repair or replace igniter. Wait for recovery
59 Line Voltage error - voltage out of specification high or low (15-37V (44-66Hz)) Applies only to thermostats having on-board transformer. Wait for recovery
60 Polarity is wrong in this case. Thermostat input higher than threshold. Wait for recovery
61 Line voltage unstable - possibly too may heavy loads switching on and off causing erratic supply voltage. Wait for recovery
62 Soft lockout: maximum number of retries exceeded. Soft lockout is reset after one hour if alarm reason disappears. Soft lockout
63 Soft lockout: maximum number of recycles exceeded. Soft lockout
64 Soft Lockout - electronics failure. On-board self diagnostics detected error. Soft lockout
65 Over temperature error. Sensor measured temperature in excess of maximum allowable limit. Soft lockout

Troubleshooting and error codes

Error Codes
Error Code Number Definition Consequence
4 Flame current too low. Check for flame. Non critical alarm
6 Flame sensed out of normal sequence (before opening or after closing gas valve). Soft lockout
18 Gas valve relays welded. Five consecutive soft lockouts. Hard lockout
23 Flame sensed during prepurge (before gas valve signaled opened). Soft lockout
32 Sensor 1 error. Temperature sensor in well is not reading correctly. Verify it is connected to board. Replace if necessary. Wait for recovery
55 Atmospheric damper end switch failed to close (end switch contacts stuck open). Wait for recovery
56 Atmospheric damper end switch failed to open (end switch contacts stuck close). Wait for recovery
57 Igniter flame rod shorted to burner ground Wait for recovery
58 Igniter flame rod shorted to burner ground. Repair or replace igniter. Wait for recovery
59 Line Voltage error - voltage out of specification high or low (15-37V (44-66Hz)) Applies only to thermostats having on-board transformer. Wait for recovery
60 Polarity is wrong in this case. Thermostat input higher than threshold. Wait for recovery
61 Line voltage unstable - possibly too may heavy loads switching on and off causing erratic supply voltage. Wait for recovery
62 Soft lockout: maximum number of retries exceeded. Soft lockout is reset after one hour if alarm reason disappears. Soft lockout
63 Soft lockout: maximum number of recycles exceeded. Soft lockout
64 Soft Lockout - electronics failure. On-board self diagnostics detected error. Soft lockout
65 Over temperature error. Sensor measured temperature in excess of maximum allowable limit. Soft lockout