This furnace is equipped with an automatic hot surface ignition system. When the thermostat calls for heat, the combustion air inducer starts, followed by a pre-purge and ignitor warm-up. The gas valve opens, gas is ignited, and the flame sensor proves the flame. The blower motor then starts after a delay to circulate warm air. The heating process continues until the thermostat is satisfied.

Troubleshooting and error codes

Diagnostic Codes

Desktop View (1024px)

Diagnostic Codes/Status of Equipment

Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E000 No errors in memory. N/A
E105 Device communication problem - No other devices on RS BUS (Communicating systems only) Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.
E110 Low line voltage Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.
E111 Line voltage polarity reversed Reverse line power voltage wiring. System resumes normal operation 5 seconds after fault recovered.
E112 Ground not detected System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.
E113 High line voltage Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5 seconds after fault recovered.
E114 Line voltage frequency out-of-range. No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5 seconds after fault recovered.
E115 Low 24V 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.
E117 Poor ground detected (Warning only) Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered
E120 Unresponsive device (Communicating systems only) Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry
E124 Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only). Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heartbeat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.
E125 Control failed self-check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc) Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.
E131 Corrupted control parameters (Verify configuration of system) (Communicating systems only). Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.
E180 Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only) Compare outdoor sensor resistance to temperature resistance charts in unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About ' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.
E200 Hard Lock out - Rollout circuit open or previously open Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.
E201 Indoor blower/communication failure - Unable to communicate with blower motor Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.
E202 Indoor blower motor mis-match - indoor motor horsepower does not match unit capacity Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming)
E203 Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart. No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming)
E204 Gas valve mis-wired Check gas valve operation and wiring. Clears when repaired
E205 Gas valve control relay contact shorted Check wiring on control and gas valve. If wiring is correct replace control.
E207 Hot surface igniter sensed open - Refer to troubleshooting Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.
E223 Low pressure switch failed open Check pressure(inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.
E224 Low pressure switch failed closed -Refer to troubleshooting Check pressure(inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.
E225 High pressure switch failed open -Refer to troubleshooting Check pressure(inches W.C) of high pressure switch closing on heat call. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.
E226 High pressure switch failed closed -Refer to troubleshooting Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restrictio. Resumes normal operation after fault is cleared.

Troubleshooting and error codes

Diagnostic Codes

Desktop View (1024px)

Diagnostic Codes/Status of Equipment

Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E000 No errors in memory. N/A
E105 Device communication problem - No other devices on RS BUS (Communicating systems only) Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.
E110 Low line voltage Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.
E111 Line voltage polarity reversed Reverse line power voltage wiring. System resumes normal operation 5 seconds after fault recovered.
E112 Ground not detected System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.
E113 High line voltage Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5 seconds after fault recovered.
E114 Line voltage frequency out-of-range. No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5 seconds after fault recovered.
E115 Low 24V 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.
E117 Poor ground detected (Warning only) Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered
E120 Unresponsive device (Communicating systems only) Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry
E124 Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only). Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heartbeat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.
E125 Control failed self-check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc) Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.
E131 Corrupted control parameters (Verify configuration of system) (Communicating systems only). Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.
E180 Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only) Compare outdoor sensor resistance to temperature resistance charts in unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About ' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.
E200 Hard Lock out - Rollout circuit open or previously open Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.
E201 Indoor blower/communication failure - Unable to communicate with blower motor Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.
E202 Indoor blower motor mis-match - indoor motor horsepower does not match unit capacity Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming)
E203 Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart. No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming)
E204 Gas valve mis-wired Check gas valve operation and wiring. Clears when repaired
E205 Gas valve control relay contact shorted Check wiring on control and gas valve. If wiring is correct replace control.
E207 Hot surface igniter sensed open - Refer to troubleshooting Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.
E223 Low pressure switch failed open Check pressure(inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.
E224 Low pressure switch failed closed -Refer to troubleshooting Check pressure(inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.
E225 High pressure switch failed open -Refer to troubleshooting Check pressure(inches W.C) of high pressure switch closing on heat call. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.
E226 High pressure switch failed closed -Refer to troubleshooting Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restrictio. Resumes normal operation after fault is cleared.