Heating Sequence of Operation:

  • Thermostat calls for heat, combustion air inducer starts.
  • Combustion air pressure switch proves blower operation.
  • 15 second pre-purge, hot surface ignitor energizes.
  • 20 second ignitor warm-up, gas valve solenoid opens.
  • 4-second "Trial for Ignition" period begins.
  • Gas ignites, flame sensor proves flame, combustion continues.
  • If flame not detected, ignition control repeats ignition trials before lockout.

Troubleshooting and error codes

Furnace Codes
Red LED Flash Code Diagnostic Codes / Status of Furnace
Off No power to control or control hardware fault detected
Heartbeat¹ Normal operation - idle, continuous fan, cool
Continuous Rapid Flash Call for heat / burner operation
1 Flash Reverse line voltage polarity
2 Flashes Improper earth ground
3 Flashes Burner failed to light, or lost flame during heat demand
4 Flashes Low flame signal - check flame sensor
5 Flashes Watchguard - burner failed to light, exceeded maximum number of retries or recycles
6 Flashes Not used
7 Flashes Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 Flashes Rollout switch open
9 Flashes Pressure switch failed to close or opened during heat demand
10 Flashes Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes Flame sensed without gas valve energized
13 Flashes Low line voltage
Off No power to control or control hardware fault detected
On Board Fault Detected
Fast Heartbeat³ Call for Heat / Burner Operation
Slow Heartbeat¹ Normal Operation - Idle, Continuous Fan, or Cool
1 Flash² Reverse Line Voltage Polarity or Phasing of 120V power
2 Flashes² Improper earth ground
3 Flashes² Burner failed to light, or lost flame during heat demand
4 Flashes² Low flame signal - check flame sensor
5 Flashes² Watchguard - burner failed to light, exceeded maximum number of retries/recycles, 1 hour lockout
6 Flashes² Not used
7 Flashes² Primary or Secondary limit switch open or Watchguard mode – Limit Switch open longer than 3 minutes
8 Flashes² Rollout switch open
9 Flashes² Pressure switch failed to close or opened during heat demand
10 Flashes² Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes² Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes² Flame sensed without gas valve energized
13 Flashes² Low line voltage

Troubleshooting and error codes

Furnace Codes
Red LED Flash Code Diagnostic Codes / Status of Furnace
Off No power to control or control hardware fault detected
Heartbeat¹ Normal operation - idle, continuous fan, cool
Continuous Rapid Flash Call for heat / burner operation
1 Flash Reverse line voltage polarity
2 Flashes Improper earth ground
3 Flashes Burner failed to light, or lost flame during heat demand
4 Flashes Low flame signal - check flame sensor
5 Flashes Watchguard - burner failed to light, exceeded maximum number of retries or recycles
6 Flashes Not used
7 Flashes Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 Flashes Rollout switch open
9 Flashes Pressure switch failed to close or opened during heat demand
10 Flashes Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes Flame sensed without gas valve energized
13 Flashes Low line voltage
Off No power to control or control hardware fault detected
On Board Fault Detected
Fast Heartbeat³ Call for Heat / Burner Operation
Slow Heartbeat¹ Normal Operation - Idle, Continuous Fan, or Cool
1 Flash² Reverse Line Voltage Polarity or Phasing of 120V power
2 Flashes² Improper earth ground
3 Flashes² Burner failed to light, or lost flame during heat demand
4 Flashes² Low flame signal - check flame sensor
5 Flashes² Watchguard - burner failed to light, exceeded maximum number of retries/recycles, 1 hour lockout
6 Flashes² Not used
7 Flashes² Primary or Secondary limit switch open or Watchguard mode – Limit Switch open longer than 3 minutes
8 Flashes² Rollout switch open
9 Flashes² Pressure switch failed to close or opened during heat demand
10 Flashes² Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes² Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes² Flame sensed without gas valve energized
13 Flashes² Low line voltage