Warranty Summary
Start-Up:
Heating Sequence:
Red LED Flash Code | Diagnostic Codes / Status of Furnace |
---|---|
LED Off | No power to control or control hardware fault detected |
Heartbeat¹ | Control powered - displayed during all modes of operation if no errors are detected |
1 Flash | Reverse line voltage polarity |
2 Flashes | Improper earth ground |
3 Flashes | Burner failed to light, or lost flame during heat demand |
4 Flashes | Low flame signal - check flame sensor |
5 Flashes | Watchguard - burner failed to light, exceeded maximum number of retries or recycles |
6 Flashes | Not used |
7 Flashes | Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes |
8 Flashes | Rollout switch open |
9 Flashes | Pressure switch failed to close or opened during heat demand |
10 Flashes | Watchguard - Pressure switch opened 5 times during one heat demand |
11 Flashes | Pressure switch stuck closed prior to activation of combustion air inducer |
12 Flashes | Flame sensed without gas valve energized |
13 Flashes | Low line voltage |
Red LED Flash Code² | Diagnostic Codes / Status of Furnace |
---|---|
LED Off | No power to control or control hardware fault detected |
Heartbeat¹ | Normal operation - idle, continuous fan, cool |
Continuous Rapid Flash | Call for heat / burner operation |
1 Flash | Reverse line voltage polarity |
2 Flashes | Improper earth ground |
3 Flashes | Burner failed to light, or lost flame during heat demand |
4 Flashes | Low flame signal - check flame sensor |
5 Flashes | Watchguard - burner failed to light, exceeded maximum number of retries or recycles |
6 Flashes | Not used |
7 Flashes | Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes |
8 Flashes | Rollout switch open |
9 Flashes | Pressure switch failed to close or opened during heat demand |
10 Flashes | Watchguard - Pressure switch opened 5 times during one heat demand |
11 Flashes | Pressure switch stuck closed prior to activation of combustion air inducer |
12 Flashes | Flame sensed without gas valve energized |
13 Flashes | Low line voltage |
Red LED Flash Code | Diagnostic Codes / Status of Furnace |
---|---|
LED Off | No power to control or control hardware fault detected |
Heartbeat¹ | Control powered - displayed during all modes of operation if no errors are detected |
1 Flash | Reverse line voltage polarity |
2 Flashes | Improper earth ground |
3 Flashes | Burner failed to light, or lost flame during heat demand |
4 Flashes | Low flame signal - check flame sensor |
5 Flashes | Watchguard - burner failed to light, exceeded maximum number of retries or recycles |
6 Flashes | Not used |
7 Flashes | Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes |
8 Flashes | Rollout switch open |
9 Flashes | Pressure switch failed to close or opened during heat demand |
10 Flashes | Watchguard - Pressure switch opened 5 times during one heat demand |
11 Flashes | Pressure switch stuck closed prior to activation of combustion air inducer |
12 Flashes | Flame sensed without gas valve energized |
13 Flashes | Low line voltage |
Red LED Flash Code² | Diagnostic Codes / Status of Furnace |
---|---|
LED Off | No power to control or control hardware fault detected |
Heartbeat¹ | Normal operation - idle, continuous fan, cool |
Continuous Rapid Flash | Call for heat / burner operation |
1 Flash | Reverse line voltage polarity |
2 Flashes | Improper earth ground |
3 Flashes | Burner failed to light, or lost flame during heat demand |
4 Flashes | Low flame signal - check flame sensor |
5 Flashes | Watchguard - burner failed to light, exceeded maximum number of retries or recycles |
6 Flashes | Not used |
7 Flashes | Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes |
8 Flashes | Rollout switch open |
9 Flashes | Pressure switch failed to close or opened during heat demand |
10 Flashes | Watchguard - Pressure switch opened 5 times during one heat demand |
11 Flashes | Pressure switch stuck closed prior to activation of combustion air inducer |
12 Flashes | Flame sensed without gas valve energized |
13 Flashes | Low line voltage |