Start-Up:

  • Set thermostat to lowest setting.
  • Turn off electrical power.
  • Turn gas valve to OFF, wait 5 minutes.
  • Turn gas valve to ON.
  • Restore electrical power.
  • Set thermostat to desired temperature.

Heating Sequence:

  • Thermostat calls for heat.
  • Combustion air blower starts.
  • Pressure switch proves blower.
  • 15-second pre-purge.
  • Hot surface ignitor energizes.
  • 20-second ignitor warm-up.
  • Gas valve opens (4-second trial for ignition).
  • Flame is ignited and sensed.
  • Combustion process continues.

Troubleshooting and error codes

Furnace Codes
Red LED Flash Code Diagnostic Codes / Status of Furnace
LED Off No power to control or control hardware fault detected
Heartbeat¹ Control powered - displayed during all modes of operation if no errors are detected
1 Flash Reverse line voltage polarity
2 Flashes Improper earth ground
3 Flashes Burner failed to light, or lost flame during heat demand
4 Flashes Low flame signal - check flame sensor
5 Flashes Watchguard - burner failed to light, exceeded maximum number of retries or recycles
6 Flashes Not used
7 Flashes Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 Flashes Rollout switch open
9 Flashes Pressure switch failed to close or opened during heat demand
10 Flashes Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes Flame sensed without gas valve energized
13 Flashes Low line voltage

Red LED Flash Code² Diagnostic Codes / Status of Furnace
LED Off No power to control or control hardware fault detected
Heartbeat¹ Normal operation - idle, continuous fan, cool
Continuous Rapid Flash Call for heat / burner operation
1 Flash Reverse line voltage polarity
2 Flashes Improper earth ground
3 Flashes Burner failed to light, or lost flame during heat demand
4 Flashes Low flame signal - check flame sensor
5 Flashes Watchguard - burner failed to light, exceeded maximum number of retries or recycles
6 Flashes Not used
7 Flashes Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 Flashes Rollout switch open
9 Flashes Pressure switch failed to close or opened during heat demand
10 Flashes Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes Flame sensed without gas valve energized
13 Flashes Low line voltage

Troubleshooting and error codes

Furnace Codes
Red LED Flash Code Diagnostic Codes / Status of Furnace
LED Off No power to control or control hardware fault detected
Heartbeat¹ Control powered - displayed during all modes of operation if no errors are detected
1 Flash Reverse line voltage polarity
2 Flashes Improper earth ground
3 Flashes Burner failed to light, or lost flame during heat demand
4 Flashes Low flame signal - check flame sensor
5 Flashes Watchguard - burner failed to light, exceeded maximum number of retries or recycles
6 Flashes Not used
7 Flashes Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 Flashes Rollout switch open
9 Flashes Pressure switch failed to close or opened during heat demand
10 Flashes Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes Flame sensed without gas valve energized
13 Flashes Low line voltage

Red LED Flash Code² Diagnostic Codes / Status of Furnace
LED Off No power to control or control hardware fault detected
Heartbeat¹ Normal operation - idle, continuous fan, cool
Continuous Rapid Flash Call for heat / burner operation
1 Flash Reverse line voltage polarity
2 Flashes Improper earth ground
3 Flashes Burner failed to light, or lost flame during heat demand
4 Flashes Low flame signal - check flame sensor
5 Flashes Watchguard - burner failed to light, exceeded maximum number of retries or recycles
6 Flashes Not used
7 Flashes Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 Flashes Rollout switch open
9 Flashes Pressure switch failed to close or opened during heat demand
10 Flashes Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes Flame sensed without gas valve energized
13 Flashes Low line voltage