Heating Sequence of Operation:

  • Thermostat calls for heat, combustion air inducer starts.
  • Combustion air pressure switch proves blower operation.
  • After a 15 second pre-purge, the hot surface ignitor energizes.
  • After a 20 second ignitor warm-up period, the gas valve solenoid opens.
  • Gas is ignited, flame sensor proves the flame, and combustion continues.
  • If flame is not detected after the first trial, the ignition control will repeat steps and then lockout.

Troubleshooting and error codes

Red LED Flash Code2 Diagnostic Codes / Status of Furnace
Off No power to control or control hardware fault detected
Heartbeat¹ Normal operation - idle, continuous fan, cool
Continuous Rapid Flash Call for heat / burner operation
1 Flash Reverse line voltage polarity
2 Flashes Improper earth ground
3 Flashes Burner failed to light, or lost flame during heat demand
4 Flashes Low flame signal - check flame sensor
5 Flashes Watchguard - burner failed to light, exceeded maximum number of retries or recycles
6 Flashes Not used
7 Flashes Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 Flashes Rollout switch open
9 Flashes Pressure switch failed to close or opened during heat demand
10 Flashes Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes Flame sensed without gas valve energized
13 Flashes Low line voltage

Troubleshooting and error codes

Red LED Flash Code2 Diagnostic Codes / Status of Furnace
Off No power to control or control hardware fault detected
Heartbeat¹ Normal operation - idle, continuous fan, cool
Continuous Rapid Flash Call for heat / burner operation
1 Flash Reverse line voltage polarity
2 Flashes Improper earth ground
3 Flashes Burner failed to light, or lost flame during heat demand
4 Flashes Low flame signal - check flame sensor
5 Flashes Watchguard - burner failed to light, exceeded maximum number of retries or recycles
6 Flashes Not used
7 Flashes Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 Flashes Rollout switch open
9 Flashes Pressure switch failed to close or opened during heat demand
10 Flashes Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes Flame sensed without gas valve energized
13 Flashes Low line voltage