Warranty Summary
| Fault Condition | Indication to Fire Panel |
|---|---|
| PowerBoost1 fault | Telco 2 is cut. |
| AC Loss | Telco 2 is cut. |
| Power Supply fault | Telco 2 is cut. |
| Low Battery | Telco 2 is cut. |
| Loss of ECP (Wiring or Addressing) | Telco 1 and 2 are cut. |
| Radio not registered | Telco 1 and 2 are cut. |
| Communicator fault | Telco 1 and 2 are cut. |
| Failure of the communications path when IP only or Cell only is programmed as a communications path. | Telco 1 and 2 are cut. |
| Failure of both communications paths when IP&Cell is programmed as a communications path. | Telco 1 and 2 are cut. |
| Failure of one of the communication paths when IP and Cell are enabled as the communications path. | Telco 2 is cut. |
| Dialer Capture Module buffer is full. | Hang up. (Panel will retry, giving the buffer a chance to empty.) |