Manual for FL-PS6(C) & FL-PS10(C)

Manual for FL-PS6(C) & FL-PS10(C)

Brand: Honeywell

Category: Security System

Document Type: Manual

Language: EN

Available Languages: EN , ES

Uploaded: Nov. 21, 2025, 6:03 p.m.

Manual Publish Date: 2021-03-29

Warranty Information

Manufacturer warrants products free from defects for 36 months from the date of manufacture.

The FL-PS series power supplies are designed to provide 24 VDC remote power and battery charging for Notification Appliance Circuits (NACs) and other system components. They can be configured for Class B or Class A wiring and support various programming options for features like strobe synchronization, selective silence, and door holder control. The units offer supervised inputs for control signals from a Fire Alarm Control Panel (FACP) or other modules, and provide trouble relays for monitoring system faults such as AC loss, battery issues, and ground faults.

Key operational aspects include:

  • Configurable NAC outputs for signaling devices or auxiliary power.
  • Input circuits for receiving control signals (e.g., polarity reversal from FACP).
  • Integral battery charger for lead-acid batteries.
  • Ground fault detection and reporting (configurable).
  • Selectable strobe synchronization options.
  • Cascading capability to expand system capacity.

Troubleshooting and error codes

Circuit Fault Trip Resistance (in ohms) Restore Value
NAC 1-5/7 Short 1.6K or lower 1.7K or higher
NAC 1-5/7 Open 55K or higher 33K or lower
ZNAC-PS 1-5/7 Short 1.6K or lower 1.7K or higher
ZNAC-PS 1-5/7 Open 45K or higher 21K or lower