| Category | Item | Cause | Countermeasure |
|---|---|---|---|
| Refrigeration System | Low discharge pressure | 1. Low ambient temperature | 1. Check the fan speed control. |
| 2. Low pressure on the suction side | 2. Check the refrigerant charge. | ||
| 3. Dirty air filter | 3. Clean the filter. | ||
| 4. Low refrigerant charge | 4. Check for refrigerant leaks and recharge. | ||
| High discharge pressure | 1. High ambient temperature | 1. Check the fan operation and condenser cleanliness. | |
| 2. Dirty condenser | 2. Clean the condenser. | ||
| 3. Overcharge of refrigerant | 3. Check and adjust refrigerant charge. | ||
| 4. Obstruction in the refrigerant circuit | 4. Check and remove obstructions. | ||
| Electrical System | Compressor not starting | 1. Power supply issue | 1. Check power supply and circuit breaker. |
| 2. Safety device tripped (e.g., overload protector) | 2. Reset or replace the safety device after investigating the cause. | ||
| 3. Control circuit issue | 3. Check control wiring and components. | ||
| Fan not running | 1. Power supply issue | 1. Check power supply and circuit breaker. | |
| 2. Motor issue | 2. Check or replace the fan motor. | ||
| 3. Control issue | 3. Check the control signals to the fan. |